Carrier gas furnace code 31.6: High pressure switch open

Gas furnace, Canada and United States

The high (secondary) pressure switch did not close for one minute after the gas valve closed, or it reopened. The 59TN6C and 58TN0B labels add that it failed to close within 75 seconds when high heat is required.

This needs a licensed gas technician. There are a few safe checks you can do first, marked below. Anything inside the unit is a job for a professional.

This involves the flue or exhaust. A blocked or leaking flue can let carbon monoxide into the home.

Only some models show this code. Check the list below.

What causes it

InteliSense display furnaces

  1. A restricted or wrongly sized vent, or strong wind at the vent.

    Check the vent and air intake pipes outside are clearYou can do this

    1. Find where the furnace vent pipe ends outside the house. A two-pipe (direct-vent) installation also has an air intake pipe ending outside.
      Check only what you can see from the ground. Do not climb onto the roof or use a ladder. If the vent ends on the roof or goes into a chimney, book a technician to check it.
    2. Check nothing is blocking or covering the ends of the pipes, in any season, and clear anything stored or growing around them.
    3. On a condensing furnace with a one-pipe installation, also check the combustion-air pipe next to the furnace is not blocked and nothing is crowding the air openings around the furnace.
    4. If a pipe is blocked inside, has holes or has come apart, do not run the furnace. Call your dealer.
      A blocked, holed or disconnected vent pipe can let toxic fumes into your home.

    Book a licensed gas technician

  2. Disconnected or blocked pressure tubing, or a faulty pressure switch.

    Book a licensed gas technician

  3. A failed inducer motor.

    Book a licensed gas technician

  4. On condensing furnaces, a plugged condensate drain or water lying in a sagging vent pipe.

    Book a licensed gas technician

  5. Not enough combustion air.

    Book a licensed gas technician

  6. A faulty pressure switch relay on the control, or a mis-wired gas valve.

    Book a licensed gas technician

InteliSense modulating furnaces

  1. A restricted or wrongly sized vent, or strong wind at the vent.

    Same check as above: Check the vent and air intake pipes outside are clear

    Book a licensed gas technician

  2. Disconnected or blocked pressure tubing, or a faulty pressure switch.

    Book a licensed gas technician

  3. A failed inducer motor.

    Book a licensed gas technician

  4. A plugged condensate drain or water lying in a sagging vent pipe.

    Book a licensed gas technician

  5. Not enough combustion air.

    Book a licensed gas technician

How to read this code on your unit

The three-digit display sits on the furnace control behind the blower door. Through the sight glass in the door you see only the status light, which flashes the first two digits of the code. Count the short flashes for the first digit, then the long flashes for the second, so 3 short flashes followed by 3 long flashes is a 33.x code. Write down what you see before you open the door or switch the furnace off. The full code with its third digit shows on the control display only with the door removed and the door switch closed, which is a job for a technician. A technician can also look back at the last 7 faults in the FLt menu. Stored codes are erased by themselves after 72 hours of powered operation after the last fault, and the display shows non when no fault is stored.

Booking a licensed gas technician

Book a licensed gas technicianlicensed gas technician

  1. Turn the unit off and leave the covers on. Gas components must only be serviced by a licensed technician.
  2. Note the code, how often it appears, and the model and serial numbers from the rating label.
  3. Book a licensed gas technician and give them those details.

Models that show this code

62 models in 7 ranges
RangeModels
58TN0B/58TN1B58TN0B045C17-12, 58TN0B070C14-12, 58TN0B070C17-16, 58TN0B070C21-20, 58TN0B090C17-16, 58TN0B090C21-20, 58TN0B110C21-20, 58TN0B135C24-22, 58TN1B045C17-12, 58TN1B070C14-12, 58TN1B070C17-16, 58TN1B070C21-20, 58TN1B090C17-16, 58TN1B090C21-20, 58TN1B110C21-20, 58TN1B135C24-22
58TP0B/58TP1B58TP0B045V14-12, 58TP0B070V14-12, 58TP0B070V17-16, 58TP0B090V17-16, 58TP0B090V21-20, 58TP0B110V21-22, 58TP0B135V24-22, 58TP1B045V14-12, 58TP1B070V14-12, 58TP1B070V17-16, 58TP1B090V17-16, 58TP1B090V21-20, 58TP1B110V21-22, 58TP1B135V24-22
59TN6C59TN6C040C14-10, 59TN6C060C17-14, 59TN6C080C17-14, 59TN6C080C21-20, 59TN6C100C21-22, 59TN6C120C24-22
59TN7A59TN7A060C17-16, 59TN7A080C17-16, 59TN7A080C21-20, 59TN7A100C21-22, 59TN7A120C24-22
59TP6C59TP6C040V14-10, 59TP6C040V17-12, 59TP6C060V14-12, 59TP6C060V17-16, 59TP6C080V17-16, 59TP6C080V21-20, 59TP6C100V21-20, 59TP6C100V21-22, 59TP6C120V24-22
59TP7A59TP7A060V17-16, 59TP7A080V17-16, 59TP7A080V21-20, 59TP7A100V21-20, 59TP7A100V21-22, 59TP7A120V24-22
59MN7C59MN7C060C17-14, 59MN7C060C21-20, 59MN7C080C17-14, 59MN7C080C21-20, 59MN7C100C21-22, 59MN7C120C24-22

Where this comes from

Checked against the manufacturer's manual on 11 October 2026.

Report a mistake on this page

Other Carrier gas furnace codes

Code Meaning What you can do
31 Flue or venting fault (depends on model) Safe checks first, then a pro
23.6 Medium pressure switch stuck closed Call a pro
31.1 Flue or venting fault (depends on model) Depends on your model
31.2 Flue or venting fault (depends on model) Depends on your model
31.3 Secondary pressure switch lockout after 3 failed trials Safe checks first, then a pro
31.4 Loss of pressure before the blower started Safe checks first, then a pro
31.5 Loss of pressure after the blower started Safe checks first, then a pro
31.7 High heat only, high switch failed to close in time Safe checks first, then a pro
32.1 Main pressure switch (LPS) open Safe checks first, then a pro
32.2 Low pressure switch open Safe checks first, then a pro
42.1 No inducer speed at start-up Call a pro
42.2 Inducer speed lost while running Call a pro

See all flue or venting fault codes on gas furnaces across brands.