Carrier gas furnace code 15: Blower motor lockout
Gas furnace, Canada and United States
In two heating cycles in a row, the blower failed to reach 250 rpm or failed to communicate with the control within 30 seconds of being turned on. The control locks out and retries by itself after 3 hours. See code 41.
On the status light, this code is 1 short flash, then 5 long flashes.
This needs a licensed gas technician. There is nothing safe to check yourself. Leave the covers on and book a professional.
Only some models show this code. Check the list below.
What causes it
Standard amber-LED furnaces
-
The blower wheel is loose or rubbing.
-
A wiring fault between the furnace control and the blower motor.
-
A failed blower control module or blower motor, or a failed furnace control.
Ultra-low NOx furnaces
-
A fault in the blower motor or its wiring, or in the furnace control. The component test on the label points a technician at the blower, its wiring and the control.
How to read this code on your unit
The amber status light (red on some older boards) on the furnace control shows through a small window in the blower access door. A steady light means the control has power and no fault to show. A code is two digits. Count the short flashes for the first digit, then the long flashes for the second, so 3 short flashes followed by 3 long flashes is code 33, and 1 short then 1 long is code 11. Write the code down before you open the door or switch the furnace off.
Booking a licensed gas technician
Book a licensed gas technicianlicensed gas technician
- Turn the unit off and leave the covers on. Gas components must only be serviced by a licensed technician.
- Note the code, how often it appears, and the model and serial numbers from the rating label.
- Book a licensed gas technician and give them those details.
Models that show this code
50 models in 7 ranges
| Range | Models |
|---|---|
| 58CVA/CVX | 58CVA070-12, 58CVA090-16, 58CVA110-20, 58CVA135-22, 58CVA155-22, 58CVX070-12, 58CVX090-16, 58CVX110-20, 58CVX135-22, 58CVX155-22 |
| 58TN0A/58TN1A | 58TN0A045C17-12, 58TN0A070C14-12, 58TN0A070C17-16, 58TN0A070C21-20, 58TN0A090C17-16, 58TN0A090C21-20, 58TN0A110C21-20, 58TN0A135C24-22, 58TN1A045C17-12, 58TN1A070C14-12, 58TN1A070C17-16, 58TN1A070C21-20, 58TN1A090C17-16, 58TN1A090C21-20, 58TN1A110C21-20, 58TN1A135C24-22 |
| 59MN7A | 59MN7A060V17-14, 59MN7A080V17-14, 59MN7A060V21-20, 59MN7A080V21-20, 59MN7A100V21-22, 59MN7A120V24-22 |
| 59MN7B | 59MN7B060C17-14, 59MN7B060C21-20, 59MN7B080C17-14, 59MN7B080C21-20, 59MN7B100C21-22, 59MN7B120C24-22 |
| 59TN6B | 59TN6B060C17-14, 59TN6B080C17-14, 59TN6B080C21-20, 59TN6B100C21-22, 59TN6B120C24-22 |
| 58CU0A | 58CU0A040C17-12, 58CU0A060C17-16, 58CU0A080C21-20, 58CU0A100C21-20 |
| 59CU5A | 59CU5A060C17-16, 59CU5A080C21-20, 59CU5A100C21-22 |
Where this comes from
- 58CVA/CVX variable-speed induced-combustion gas furnace, installation, start-up, operating and service instructions (58CV-13SI) , page 37, 57, 58
- 59MN7A modulating condensing gas furnace, installation, start-up, operating and service instructions (59MN7A-12SI) , page 72, 90, 91
- 58CU0A 80% communicating ultra-low NOx gas furnace, installation, start-up, operating and service instructions (58CU0A-03SI) , page 23
- 59CU5A single-stage communicating ultra-low NOx condensing gas furnace, installation, start-up, operating and service instructions (59CU5A-01SI) , page 53, 65
Checked against the manufacturer's manual on 9 October 2026.
Other Carrier gas furnace codes
| Code | Meaning | What you can do |
|---|---|---|
| 11 | No previous fault stored | You can often fix it |
| 13 | Limit circuit lockout (depends on model) | Safe checks first, then a pro |
| 14 | Ignition lockout after repeated failed lighting attempts | Safe checks first, then a pro |
| 21 | Gas heating lockout, fault in the gas valve circuit | Safe checks first, then a pro |
| 22 | Flame sensed while the gas valve is off | Safe checks first, then a pro |
| 23 | Flue or venting fault (depends on model) | Call a pro |
| 41 | Blower motor fault, speed or communication lost | Call a pro |
| 15.1 | Blower lockout, no blower speed signal | Call a pro |
| 15.2 | Blower lockout, blower never reached 500 rpm | Call a pro |
| 41.1 | No blower speed at start-up | Call a pro |
| 41.2 | Blower speed lost while running | Call a pro |
| 41.3 | Blower not reaching 500 rpm | Call a pro |
See all fan or blower fault codes on gas furnaces across brands.