Carrier gas furnace code 32: Low or low-heat pressure switch did not close, or opened again
Gas furnace, Canada and United States
The low pressure switch (the low-heat switch on two-stage boards) did not close, or opened during heating. Depending on the board, the inducer stops for 15 minutes before a retry if the switch stays open for 5 minutes, or the next heating cycle is held at high heat if it opens within 5 minutes of ignition.
On the status light, this code is 3 short flashes, then 2 long flashes.
This needs a licensed gas technician. There are a few safe checks you can do first, marked below. Anything inside the unit is a job for a professional.
This involves the flue or exhaust. A blocked or leaking flue can let carbon monoxide into the home.
Only some models show this code. Check the list below.
What causes it
-
A restricted or wrongly sized vent, or strong wind at the vent.
Check the vent and air intake pipes outside are clearYou can do this
- Find where the furnace vent pipe ends outside the house. A two-pipe (direct-vent) installation also has an air intake pipe ending outside. Check only what you can see from the ground. Do not climb onto the roof or use a ladder. If the vent ends on the roof or goes into a chimney, book a technician to check it.
- Check nothing is blocking or covering the ends of the pipes, in any season, and clear anything stored or growing around them.
- On a condensing furnace with a one-pipe installation, also check the combustion-air pipe next to the furnace is not blocked and nothing is crowding the air openings around the furnace.
- If a pipe is blocked inside, has holes or has come apart, do not run the furnace. Call your dealer. A blocked, holed or disconnected vent pipe can let toxic fumes into your home.
- Find where the furnace vent pipe ends outside the house. A two-pipe (direct-vent) installation also has an air intake pipe ending outside.
-
On condensing furnaces, a plugged condensate drain or water lying in a sagging vent pipe.
-
Disconnected or blocked pressure tubing, mis-wired pressure switches, or a switch that has failed or is out of calibration.
-
A faulty inducer motor, or low voltage to it.
-
Not enough combustion air, or an air leak between the burner compartment and the blower compartment.
-
Low inlet gas pressure, on furnaces fitted with a low gas pressure switch.
How to read this code on your unit
The amber status light (red on some older boards) on the furnace control shows through a small window in the blower access door. A steady light means the control has power and no fault to show. A code is two digits. Count the short flashes for the first digit, then the long flashes for the second, so 3 short flashes followed by 3 long flashes is code 33, and 1 short then 1 long is code 11. Write the code down before you open the door or switch the furnace off.
Booking a licensed gas technician
Book a licensed gas technicianlicensed gas technician
- Turn the unit off and leave the covers on. Gas components must only be serviced by a licensed technician.
- Note the code, how often it appears, and the model and serial numbers from the rating label.
- Book a licensed gas technician and give them those details.
Models that show this code
142 models in 14 ranges
| Range | Models |
|---|---|
| 58CTA/CTX | 58CTA045-08, 58CTA045-12, 58CTA070-08, 58CTA070-12, 58CTA070-16, 58CTA090-14, 58CTA090-16, 58CTA090-20, 58CTA110-12, 58CTA110-16, 58CTA110-22, 58CTA135-16, 58CTA135-22, 58CTA155-20, 58CTX045-08, 58CTX045-12, 58CTX070-08, 58CTX070-12, 58CTX070-16, 58CTX090-14, 58CTX090-16, 58CTX090-20, 58CTX110-12, 58CTX110-16, 58CTX110-22, 58CTX135-16, 58CTX135-22, 58CTX155-20 |
| 58CVA/CVX | 58CVA070-12, 58CVA090-16, 58CVA110-20, 58CVA135-22, 58CVA155-22, 58CVX070-12, 58CVX090-16, 58CVX110-20, 58CVX135-22, 58CVX155-22 |
| 58TN0A/58TN1A | 58TN0A045C17-12, 58TN0A070C14-12, 58TN0A070C17-16, 58TN0A070C21-20, 58TN0A090C17-16, 58TN0A090C21-20, 58TN0A110C21-20, 58TN0A135C24-22, 58TN1A045C17-12, 58TN1A070C14-12, 58TN1A070C17-16, 58TN1A070C21-20, 58TN1A090C17-16, 58TN1A090C21-20, 58TN1A110C21-20, 58TN1A135C24-22 |
| 58TP0A/58TP1A | 58TP0A045V14-12, 58TP0A070V14-12, 58TP0A070V17-16, 58TP0A090V17-16, 58TP0A090V21-20, 58TP0A110V21-22, 58TP0A135V24-22, 58TP1A045V14-12, 58TP1A070V14-12, 58TP1A070V17-16, 58TP1A090V17-16, 58TP1A090V21-20, 58TP1A110V21-22, 58TP1A135V24-22 |
| 59MN7A | 59MN7A060V17-14, 59MN7A080V17-14, 59MN7A060V21-20, 59MN7A080V21-20, 59MN7A100V21-22, 59MN7A120V24-22 |
| 59MN7B | 59MN7B060C17-14, 59MN7B060C21-20, 59MN7B080C17-14, 59MN7B080C21-20, 59MN7B100C21-22, 59MN7B120C24-22 |
| 59SC2D | 59SC2D040E14-10, 59SC2D040E17-12, 59SC2D060E14-12, 59SC2D060E17-14, 59SC2D080E17-16, 59SC2D080E21-20, 59SC2D100E21-20, 59SC2D100E21-22, 59SC2D120E24-20 |
| 59SC5B | 59SC5B026E14-10, 59SC5B040E14-10, 59SC5B040E17-12, 59SC5B060E14-12, 59SC5B060E17-16, 59SC5B080E17-16, 59SC5B080E21-20, 59SC5B100E21-20, 59SC5B100E21-22, 59SC5B120E24-22, 59SC5B140E24-22 |
| 59SP6A | 59SP6A040V14-10, 59SP6A040V17-12, 59SP6A060V14-12, 59SP6A060V17-14, 59SP6A080V17-16, 59SP6A080V21-20, 59SP6A100V21-20, 59SP6A120V24-22 |
| 59TN6A | 59TN6A060V17-14, 59TN6A080V17-14, 59TN6A080V21-20, 59TN6A100V21-22, 59TN6A120V24-22 |
| 59TN6B | 59TN6B060C17-14, 59TN6B080C17-14, 59TN6B080C21-20, 59TN6B100C21-22, 59TN6B120C24-22 |
| 59TP5A | 59TP5A040E14-10, 59TP5A060E14-12, 59TP5A040E17-12, 59TP5A060E17-14, 59TP5A080E17-16, 59TP5A080E21-20, 59TP5A100E21-20, 59TP5A120E24-22 |
| 59TP6A | 59TP6A040V14-10, 59TP6A040V14-12, 59TP6A060V17-12, 59TP6A060V17-14, 59TP6A080V17-16, 59TP6A080V21-20, 59TP6A100V21-20, 59TP6A120V24-22 |
| 59TP6B | 59TP6B040V14-10, 59TP6B040V17-12, 59TP6B060V14-12, 59TP6B060V17-14, 59TP6B080V17-16, 59TP6B080V21-20, 59TP6B100V21-20, 59TP6B120V24-22 |
Where this comes from
- 59SC5B single-stage 35-in. condensing gas furnace, installation, start-up, operating and service instructions (59SC5B-05SI) , page 69
- 58CTA/CTX two-stage induced-combustion gas furnace, installation, start-up, operating and service instructions (58CT-12SI) , page 45
- 59TP6A two-stage variable-speed condensing gas furnace, installation, start-up, operating and service instructions (59TP6A-10SI) , page 73, 90
- 59MN7A modulating condensing gas furnace, installation, start-up, operating and service instructions (59MN7A-12SI) , page 72, 90
Checked against the manufacturer's manual on 15 October 2026.
Other Carrier gas furnace codes
| Code | Meaning | What you can do |
|---|---|---|
| 23 | Flue or venting fault (depends on model) | Call a pro |
| 31 | Flue or venting fault (depends on model) | Safe checks first, then a pro |
| 42 | Inducer motor fault | Safe checks first, then a pro |
| 43 | Lower pressure switch open while a higher one is closed | Call a pro |
| 14.4 | Lockout after repeated pressure switch openings | Safe checks first, then a pro |
| 23.1 | Flue or venting fault (depends on model) | Call a pro |
| 23.2 | Secondary pressure switch stuck closed | Call a pro |
| 23.3 | Pressure transducer senses over-pressure | Call a pro |
| 23.4 | Low pressure switch stuck closed | Call a pro |
| 23.5 | High pressure switch stuck closed | Call a pro |
| 32.1 | Main pressure switch (LPS) open | Safe checks first, then a pro |
| 32.2 | Low pressure switch open | Safe checks first, then a pro |